A cord that is too thin fails in two ways. It can carry more current than its wires are rated for, so it heats up, and it can lose so much voltage over its length that the tool at the far end runs hot and weak. Short cords usually hit the first limit; long cords hit the second. The calculator checks both.
How the calculator works
First it turns the load into amps, then it works out the voltage lost in the cord. Current flows out on one wire and back on the other, so the wire length is twice the cord length.
amps = watts ÷ volts (or the amps on the nameplate)
voltage drop = 2 × cord length (ft) × amps × ohms per 1,000 ft ÷ 1,000
drop % = voltage drop ÷ supply voltage × 100
The answer is the thinnest gauge (the highest AWG number) that is rated for the current and keeps the drop within your limit. Remember that the numbers run backwards: a 12 gauge cord is thicker than a 14 or 16 gauge one.
| Gauge | Copper area | Ohms per 1,000 ft | Typical cord rating | Usual use |
|---|---|---|---|---|
| 18 AWG | 0.82 mm² | 6.385 | 10 A | Lamps, chargers, light strings |
| 16 AWG | 1.31 mm² | 4.016 | 13 A | Hedge trimmers, drills, holiday displays |
| 14 AWG | 2.08 mm² | 2.525 | 15 A | Circular saws, mowers, shop vacs |
| 12 AWG | 3.31 mm² | 1.588 | 15 or 20 A | Long runs, table saws, pressure washers |
| 10 AWG | 5.26 mm² | 0.999 | 15 or 20 A (set by the plug) | Very long runs, compressors, generators |
Worked example: an electric pressure washer on 100 ft of cord
The washer's nameplate says 13 A at 120 V, and the outlet is 100 ft from the driveway.
- A 16 AWG cord is only rated for 13 A, and at this length it would lose 8.7 percent of the voltage. Too thin.
- A 14 AWG cord: 2 × 100 × 13 × 2.525 ÷ 1,000 = 6.6 V, or 5.5 percent. Still over the 5 percent limit.
- A 12 AWG cord: 2 × 100 × 13 × 1.588 ÷ 1,000 = 4.1 V, or 3.4 percent. The washer gets about 115.9 V. 12 AWG is the minimum.
Move the washer closer and use a 50 ft cord, and the drop on 16 AWG falls to 4.4 percent, so a 16 gauge cord passes, though only just, since 13 A is its full rating. A 14 gauge cord at 2.7 percent gives more margin. If you pick the stricter 3 percent limit, the 100 ft run needs 10 AWG.
Extension cord gauge chart by amps and length
Minimum gauge at 120 V from the same math. "None" means no ordinary cord from 18 to 10 AWG stays within the limit; bring the power closer instead.
| Load | 25 ft | 50 ft | 100 ft | 150 ft |
|---|---|---|---|---|
| 5 A (600 W) | 18 / 18 | 18 / 18 | 16 / 14 | 14 / 12 |
| 8 A (960 W) | 18 / 18 | 18 / 16 | 14 / 12 | 12 / 10 |
| 10 A (1,200 W) | 18 / 18 | 16 / 14 | 14 / 12 | 12 / 10 |
| 13 A (1,560 W) | 16 / 16 | 16 / 14 | 12 / 10 | 10 / None |
| 15 A (1,800 W) | 14 / 14 | 14 / 12 | 12 / 10 | 10 / None |
The first number is for a 5 percent drop, the second for 3 percent. Treat 18 AWG as light-duty only: many tools and outdoor uses call for at least 16 AWG regardless of the math, so follow the tool manual when it names a minimum gauge or a maximum cord length.
Reading the cord jacket
A label such as 14/3 SJTW means 14 gauge with three conductors (hot, neutral and ground). In the letters, S is service cord, J is junior (300 V) service, T is thermoplastic insulation and W means rated for outdoor use. The jacket or tag also shows the amp or watt rating; that marked rating is the real limit even if the calculator says a gauge would pass.
230 V countries
In Australia and New Zealand cords are sold by copper area in mm² instead of AWG, and the higher voltage roughly halves the current for the same watts. A 2,400 W heater-style load on a 30 m cord draws 10.4 A, loses 3.6 percent on a 16 AWG-sized conductor, and so needs a cord of at least 1.5 mm². It also draws more than 10 A, so it needs a 15 A plug, cord and outlet.
Practical tips
- Uncoil a cord fully before running a heavy load. A coiled cord cannot shed heat.
- Use one cord of the right length, not several short ones joined together; every connection adds resistance and a place for water to get in.
- For a generator, size the cord to the appliance it feeds; the generator wattage calculator helps with the watts, and our portable generator safety guide covers where the cord should run.
- For a holiday display, the Christmas lights calculator adds up the watts so you can enter them here.
Safety notes
- Plug space heaters, refrigerators, freezers and window air conditioners straight into a wall outlet unless the manufacturer says otherwise. A heater runs near its full rating for hours, which is when undersized cords and loose plugs overheat.
- A cord that feels warm, a plug that is discolored, or a breaker that trips means the load is too much. Stop and use a heavier cord or a different circuit.
- Outdoors, use cords marked W and plug into a GFCI-protected outlet. Keep connections off wet ground and out of snow.
- Do not run cords under rugs, through doorways or windows where they get pinched, or through walls and ceilings. A cord is a temporary connection; if you need power in the same place every day, have an electrician install an outlet, following local electrical code.
Frequently asked questions
What gauge extension cord do I need for 100 feet?
For a 13 to 15 amp tool at 120 V, 12 gauge keeps the voltage drop under 5 percent (3.4 percent at 13 A, 4 percent at 15 A). For a 5 amp load, 16 gauge is enough. If you want the drop under 3 percent for a motor or compressor, go to 10 gauge for 13 A or more.
Is a 16 gauge extension cord good for 100 feet?
Only for light loads. At 5 A it loses 3.3 percent, which is fine, but at 8 A the drop is 5.4 percent, so a 14 gauge cord is the better choice. Above 13 A a 16 gauge cord is over its rating at any length.
What gauge extension cord for a 15 amp tool?
14 gauge up to about 50 ft and 12 gauge at 100 ft, using a 5 percent drop limit. At 150 ft you need 10 gauge, and even that cannot hold a 3 percent drop, so run power closer if you can.
Can I use an extension cord with a space heater?
Heater manufacturers and fire safety agencies say no: plug it directly into a wall outlet. A 1,500 W heater draws 12.5 A for hours at a time, which strains cords, plugs and power strips.