What Size Generator Do You Need to Run a House?

What size generator you need to run a house depends far less on square footage than on which big loads you insist on keeping. Decide that first, then the wattage almost picks itself.

By Mohamed Elgamal · Published November 10, 2026

Start with a decision, not a number

Two houses of the same size can need very different generators. One has a gas furnace and gas water heater; the other has a well, central air and an electric water heater. Before you compare models, pick one of three plans:

  1. Essentials only. Food stays cold, the basement stays dry, the heat stays on, and you keep lights, internet and a microwave.
  2. Essentials plus one big comfort load. Add central air, or an electric water heater, or a well pump that runs the whole house's water. Each one moves you up a size class.
  3. Whole house. Every circuit stays live, including the dryer and range. This is a job for a permanent standby generator with an automatic transfer switch.

Why square footage is a poor guide

Charts that match a generator to floor area are rough at best. Floor area says nothing about whether your heat is gas or electric, whether water comes from a well, or how much of the kitchen runs on 240 volts, and those choices swing the total by thousands of watts.

Service size is not the answer either. A 200-amp, 240-volt panel could in theory deliver 200 × 240 = 48,000 W, but homes almost never draw close to that at once.

Worked example: the essentials in a house on a well

Take a house with a refrigerator, a separate freezer, a gas furnace with a ½ hp blower, a ½ hp well pump, ten LED bulbs, a TV with router and chargers, and a microwave. Using typical figures from the generator wattage calculator:

LoadRunning wattsExtra watts to start
Refrigerator7001,500
Freezer5001,000
Furnace blower, ½ hp8751,475
Well pump, ½ hp1,0001,100
Ten LED bulbs1000
TV, router, chargers2000
Microwave1,0000
Total4,375largest single jump: 1,500

Only one motor is likely to start at a time, so the peak is the running total plus the biggest single jump: 4,375 + 1,500 = 5,875 W. Keeping about 25 percent in reserve, 4,375 × 1.25 = 5,469, which rounds up to a 5,500 W running rating. That generator would sit near 80 percent of its rating with everything on, and its surge rating needs to reach at least 5,875 W.

Note what is missing: no space heater, electric water heater or air conditioning.

What the big loads add

These typical ranges show why plan 2 and plan 3 cost so much more. Always check the nameplate, because these vary widely between models.

LoadTypical running wattsNote
Central air, about 3 tonsroughly 3,000–4,000240 V; the compressor's starting surge is large
Electric water heaterabout 4,000–4,500240 V; resistance load, no surge
Electric range or oven2,000–5,000+depends on how many burners are on
Electric dryerabout 5,000240 V
Electric furnace or heat pump backup heatoften 5,000–20,000the single biggest load in many homes
Well pump, 1 hpabout 1,500–2,000check the pump label; deep wells are often 240 V

Add central air at 3,500 W and an electric water heater at 4,000 W to the example and the running total becomes 4,375 + 3,500 + 4,000 = 11,875 W. With the same 25 percent reserve that is about 14.8 kW before you account for the air conditioner's starting surge. You are now shopping for a standby unit, not a portable one. A soft-start kit on the compressor, fitted by an HVAC technician, can cut that surge substantially, and the generator maker can tell you which units start your size of air conditioner.

If you heat with electric resistance or heat pump backup strips, size for heat first: in a winter outage it is the load you cannot drop. A heat pump in mild weather draws far less than its strips; the heat pump running cost calculator shows its typical draw.

Portable or standby?

  • Portable generators commonly run from about 3,000 to 10,000 running watts. A 5,000 to 7,500 W model covers plan 1 in most homes when connected through a manual transfer switch or panel interlock.
  • Air-cooled standby generators are commonly sold from about 10 kW into the mid-20s of kW. They start on their own and run on natural gas or propane. Most produce somewhat less power on natural gas than on propane, so compare the rating for the fuel you actually have.
  • Load management lets a smaller standby unit serve a bigger house by briefly shutting off the water heater, dryer or air conditioner when the generator nears its limit. In the US, when an automatic transfer switch feeds the whole panel, the electrical code generally requires either a generator that can carry the full calculated load or automatic load management. Your electrician or inspector will confirm what applies.

Watts are only half the plan; fuel matters too. See how many kilowatt-hours your loads use in a day with the electricity cost calculator, and how long a furnace fan really runs in the cost to run a furnace blower.

Safety and code

  • Run portable generators outdoors only, far from doors, windows and vents, never in a garage or under a carport. Carbon monoxide kills quickly and has no smell. Read portable generator safety before the first outage.
  • Never backfeed through a dryer or wall outlet. Any connection to house wiring needs a transfer switch or approved interlock installed by a licensed electrician, with a permit where required. In Australia, that means a changeover switch fitted by a licensed electrician.
  • Standby generators have clearance rules from windows, vents and property lines, and a gas line sized for the unit. Check local code and the manufacturer's installation manual.
  • Keep battery-powered CO alarms working on every level of the home.

Frequently asked questions

Will a 7,500 watt generator run a house?

It will run the essentials in most homes, but usually not a whole house with central air or electric heat. Keeping it near 80 percent of its rating, 7,500 W covers about 6,000 W of running load, enough for the 4,375 W essentials example here with room to spare.

How many watts does it take to run the essentials in a house?

Often about 3,000 to 5,000 running watts. A refrigerator, freezer, furnace blower, well pump, lights, TV and microwave come to about 4,375 W running and 5,875 W at peak, which points to a 5,500 W generator.

What size generator do I need to run central air?

Plan on roughly 3,000 to 4,000 running watts for a 3-ton system on top of everything else, plus a large starting surge. With the essentials and an electric water heater as well, the running load reaches about 11,875 W, so standby sizes of about 15 kW and up come into play. A soft-start kit can lower the surge.

Do the math for your own project.

Open the generator wattage calculator