Tankless vs Tank Water Heater Sizing

Tankless vs tank water heater sizing trips people up because the two are measured in different units. A tank is sized by how many gallons it can deliver in an hour; a tankless unit is sized by how many gallons per minute it can heat at the same moment. Here is how to translate one into the other before you swap.

By Mohamed Elgamal · Published November 12, 2026

Two different questions

A tank stores hot water and reheats it slowly, so what matters is volume over time: can it get through your busiest hour? That is its first-hour rating, in gallons.

A tankless heater stores almost nothing and heats water as fast as it flows, so what matters is flow right now: how many fixtures run at once, and how many degrees the water must be warmed. That is a rating in gallons per minute (gpm) at a stated temperature rise.

TankTankless
Size it byPeak-hour demand (gallons)Simultaneous flow (gpm) at your temperature rise
Number to compareFirst-hour rating on the EnergyGuide labelFlow at a given rise, or heat output in BTU/hr or kW
Fails whenToo many uses in one hour drain itToo many fixtures at once, or very cold inlet water
Long showersLimited by stored waterNo time limit while flow stays within capacity

What size tankless water heater replaces a 50-gallon tank?

There is no single answer, because "50 gallons" describes storage, not flow. Ask instead what your 50-gallon tank actually serves at its worst moment. Two showers running together is the usual test.

Worked example: same house, two climates

A household has two showers with older 2.5 gpm heads that run at the same time on school mornings. The heater is set to 120°F and showers are mixed to about 105°F. In winter, the cold supply reaches 40°F in a northern state; a similar house on the Gulf Coast sees about 70°F.

40°F inlet70°F inlet
Share of shower water from the heater81%70%
Hot water flow for two showers4.06 gpm3.5 gpm
Temperature rise80°F50°F
Heat output neededabout 163,000 BTU/hr (47.6 kW)about 88,000 BTU/hr (25.6 kW)

The northern house needs nearly twice the heating power for the same two showers. A tank barely notices inlet temperature in the moment; a tankless unit's capacity shrinks as the water gets colder.

For a tank in that northern house, the busiest hour tells the story. Two 10-minute showers (40.6 gal from the heater), a top-load warm wash (25 gal) and a dishwasher cycle (7 gal) add up to 72.6 gallons, so you would want a first-hour rating of about 73 gallons. Run your own numbers in the water heater size calculator, which shows both the tank and tankless figures side by side.

Reading a tankless spec sheet

Makers often advertise a maximum gpm that assumes a small temperature rise. To compare honestly, convert heat output to flow at your rise:

hot water flow (gpm) = output (BTU/hr) ÷ (500 × temperature rise in °F)

Output is input times efficiency. A gas unit with a 199,000 BTU/hr input at 95% efficiency puts out about 189,000 BTU/hr. For electric units, multiply kilowatts by 3,412 to get BTU/hr.

Output35°F rise50°F rise70°F rise80°F rise
Electric 18 kW3.51 gpm2.46 gpm1.75 gpm1.54 gpm
Electric 27 kW5.26 gpm3.69 gpm2.63 gpm2.30 gpm
Electric 36 kW7.02 gpm4.91 gpm3.51 gpm3.07 gpm
Gas, 120,000 BTU/hr output6.86 gpm4.80 gpm3.43 gpm3.00 gpm
Gas, 160,000 BTU/hr output9.14 gpm6.40 gpm4.57 gpm4.00 gpm
Gas, about 189,000 BTU/hr output10.80 gpm7.56 gpm5.40 gpm4.73 gpm

Apply that to the example. In the Gulf Coast house, a 27 kW electric unit gives 3.69 gpm at a 50°F rise, enough for the 3.5 gpm the two showers need. In the northern house it gives only 2.30 gpm at an 80°F rise, a little over half of the 4.06 gpm required. There, a gas unit near 189,000 BTU/hr output (4.73 gpm) covers it, while one at 160,000 BTU/hr (4.00 gpm) falls just short on the coldest days. Swapping to 2.0 gpm showerheads would bring the demand down to 3.25 gpm.

Things a tank hides that a tankless swap exposes

  • Gas supply. A typical gas tank burner is rated in the tens of thousands of BTU/hr, while whole-house gas tankless units are commonly rated up to about 199,000 BTU/hr input. The existing gas line, and sometimes the meter, may be too small for that.
  • Venting. Tankless gas units need their own approved vent system; the old tank's flue usually cannot be reused as is.
  • Electric service. A 27 kW unit at 240 volts draws 27,000 ÷ 240 = 112.5 amps, usually split across several double-pole breakers. Many homes need a panel or service upgrade before an electric tankless can serve the whole house.
  • Minimum flow. A tankless unit only fires above a small minimum flow listed on its spec sheet. A trickle at the bathroom sink may stay cold.
  • Freezing. Units mounted outdoors or in unheated garages rely on built-in freeze protection that needs power. Plan for outages and insulate the lines; see how to keep pipes from freezing.
  • Running cost. A tank loses heat around the clock; a tankless unit does not, but draws heavily while running. Compare with your own rate in the electricity cost calculator.

Which one should you size for?

Running out during the third shower? Either type fixes it: a tank with a higher first-hour rating, or a tankless unit sized for the showers that overlap. Short on space? Tankless wins, if your gas line, vent path or panel can support it. Very cold winter water and electric only? A tank or heat pump water heater is often more practical for a whole house.

Safety and code notes

  • Gas, venting and electrical work for any water heater usually requires a permit and, in many places, a licensed installer. Check local code.
  • Keep carbon monoxide alarms working near any fuel-burning appliance.
  • Tank heaters need a working temperature and pressure relief valve; many areas also require an expansion tank. Tankless units have their own relief valve and installation requirements in the manual.
  • A 120°F setting is the common US recommendation for limiting scalds. In Australia, storage and instantaneous heaters have their own temperature rules, so follow the local plumbing standard.

Frequently asked questions

What size tankless water heater do I need to replace a 50 gallon tank?

Size it for the showers that run at the same time, not the tank's gallons. Two 2.5 gpm showers need about 4.06 gpm of 120°F water with 40°F winter supply water, roughly 163,000 BTU/hr of output. With 70°F supply water the same showers need 3.5 gpm and about 88,000 BTU/hr.

Can an electric tankless water heater replace a tank?

It depends on your climate and electric service. A 27 kW unit heats about 3.69 gpm at a 50°F rise but only about 2.30 gpm at an 80°F rise, and it draws about 112.5 amps at 240 volts, which many panels cannot spare.

Is a tank sized in gallons per hour or gallons per minute?

A tank is compared by its first-hour rating, the gallons it delivers in one hour starting full. A tankless heater is compared by gallons per minute at a given temperature rise, because it heats water only as it flows.

Do the math for your own project.